Three-Phase Power Formulas

Three-phase power is the standard way electricity is distributed to commercial and industrial equipment because it delivers more usable power per amp of wire than single-phase. The math uses either line-to-line voltage with a √3 factor or line-to-neutral voltage with a factor of 3, and both forms give the same answer because VLL = √3 × VLN. This page covers both formulas and shows how the same load looks on 208V, 240V, 480V, and 120V legs.

Formulas

P = √3 × V_L-L × I × PF
P = 3 × V_L-N × I × PF
V_L-L = √3 × V_L-N

Three-phase power uses three AC waveforms offset by 120 degrees. The √3 factor (1.732) appears because of the geometric relationship between line-to-line and line-to-neutral voltages. Three-phase delivers more power per amp than single-phase, meaning smaller wire and lower losses for the same power output.

Worked Examples

Example 1: 10kW motor at 208V (3-phase, PF 0.85)

I = 10000 / (1.732 × 0.85 × 208) = 10000 / 306.3 = 32.65A per line

Example 2: Same 10kW at 480V (3-phase, PF 0.85)

I = 10000 / (1.732 × 0.85 × 480) = 10000 / 706.9 = 14.15A per line

Example 3: 208V line-to-line to line-to-neutral

V_L-N = 208 / 1.732 = 120V (this is why 208/120V panels exist)

Common Mistakes

  • Using single-phase formula for three-phase circuits. Current is 1.732x lower than single-phase at the same power.
  • Confusing line-to-line and line-to-neutral voltage. Using the wrong one changes the result by √3.
  • Assuming 240V three-phase is the same as 240V single-phase. Three-phase 240V has different current draw.

Try the Calculator

Use the interactive kW to Amps Calculator for instant results with any values. Every result page shows the formula applied with your specific numbers.

All Formulas

This is a formula reference page for educational use. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before applying any of these formulas to real installations.

Standards & References

This page cites the following electrical codes and standards. Always consult the current edition of your local adopted standard for authoritative requirements.

  1. IEC 60038. IEC standard voltages. Defines 230/400V as the nominal low-voltage supply for 50Hz systems, which harmonized European residential supply in 1995.
    International Electrotechnical Commission. Reference →
  2. ANSI C84.1. American National Standard for Electric Power Systems and Equipment: Voltage Ratings (60 Hz). Defines the nominal system voltages (120, 208, 240, 277, 480V) and their allowable ranges at the service entrance and utilization point.
    American National Standards Institute / NEMA. Reference →
  3. NEC Table 310.16. Allowable ampacities of insulated conductors rated up to 2000V, 60°C through 90°C, not more than three current-carrying conductors in raceway or cable.
    National Electrical Code (NFPA 70), Article 310, Conductors for General Wiring. Reference →

Disclaimer: The information on this page is provided for reference. Always consult a licensed electrician and the current edition of your local adopted electrical code before performing electrical work.