Horsepower to Amps Calculator

Convert single-phase and three-phase AC motor horsepower to both the calculated running current (what the meter reads at full load) and the NEC Table 430.248 / 430.250 full-load current (what Article 430 requires for branch-circuit conductor, switch, and OCP sizing). Use the running amps for metering and energy cost. Use the table FLC for breaker and wire sizing under NEC 430.6(A)(1). DC motors are shown for reference only, NEC 430.6(A)(3) requires using the motor nameplate with Table 430.247 for DC branch-circuit sizing, so use the nameplate and a licensed electrician for actual DC installations.

= 8.6 amps running (meter)
16 amps NEC Table 430.248 FLC (code sizing)
Running: (1 × 746) ÷ (120 × 0.85 × 0.85) = 8.6 A · NEC 430.248 FLC: 16 A
See full breakdown for 1 HP at 120V
code Embed this calculator on your site

Copy this code and paste it into your website HTML. The calculator fills the width of its container and auto-resizes to fit its content.

Free to use, no attribution required beyond the built-in "Powered by WireResult" footer.

What Is HP to Amps?

Horsepower (HP) measures mechanical output. Amps measure electrical current. Every motor is rated in HP, but every circuit breaker and wire is rated in amps. This conversion bridges the gap. One HP equals 746 watts, but a motor rated at 1 HP draws more than 746W of electrical power because no motor is 100% efficient.

The Formula

Amps = (HP × 746) ÷ (Volts × Efficiency × Power Factor)

Efficiency and power factor both reduce the effective output. A motor with 85% efficiency wastes 15% as heat. A power factor of 0.85 means the motor draws reactive current that does no mechanical work. Both increase the amp draw above what a simple watts-to-amps conversion would predict.

NEC Reference Values for Motor Branch Circuits

Final conductor, breaker, disconnect, and overload selection is an install decision your electrician makes against the motor nameplate, the actual install conditions, and any 430/440 provisions. The percentages and section references below are NEC reference values for context, not prescriptive install picks. Motor branch circuits follow Article 430 of the NEC, which uses a different sizing base than general branch circuits. Three things to know:

Single-Phase Running Current

Calculated single-phase running current at 85% efficiency and PF 0.85, what the meter reads at full load on a single-phase circuit. These are not the values to use for NEC branch-circuit sizing; use the NEC Table 430.248 values further down for that.

Three-Phase Running Current

Calculated three-phase running current per line at 85% efficiency and PF 0.85, using I = (HP × 746) ÷ (√3 × VLL × Eff × PF). Links open the result page in three-phase mode. 208V, 230V, and 240V are common commercial three-phase values; 480V is common US industrial three-phase.

NEC Table 430.248 FLC, Single-Phase (Code Sizing)

Full-load current values from NEC Table 430.248 used for branch-circuit conductor, switch, and overcurrent protection sizing under NEC 430.6(A)(1). The 115V column covers 110-120V systems; the 230V column covers 220-240V. Dashes mark HP / voltage combinations not listed in the table.

HP115V
(110-120V)
200V208V230V
(220-240V)
1/6 HP4.4 A2.5 A2.4 A2.2 A
1/4 HP5.8 A3.3 A3.2 A2.9 A
1/3 HP7.2 A4.1 A4 A3.6 A
1/2 HP9.8 A5.6 A5.4 A4.9 A
3/4 HP13.8 A7.9 A7.6 A6.9 A
1 HP16 A9.2 A8.8 A8 A
1.5 HP20 A11.5 A11 A10 A
2 HP24 A13.8 A13.2 A12 A
3 HP34 A19.6 A18.7 A17 A
5 HP56 A32.2 A30.8 A28 A
7.5 HP80 A46 A44 A40 A
10 HP100 A57.5 A55 A50 A

NEC Table 430.250 FLC, Three-Phase (Code Sizing)

Full-load current values from NEC Table 430.250 (three-phase squirrel-cage / synchronous motors) used for branch-circuit conductor, switch, and overcurrent protection sizing under NEC 430.6(A)(1). The 230V column covers 220-240V; the 460V column covers 440-480V.

HP200V208V230V
(220-240V)
460V
(440-480V)
575V
1/2 HP2.5 A2.4 A2.2 A1.1 A0.9 A
3/4 HP3.7 A3.5 A3.2 A1.6 A1.3 A
1 HP4.8 A4.6 A4.2 A2.1 A1.7 A
1.5 HP6.9 A6.6 A6 A3 A2.4 A
2 HP7.8 A7.5 A6.8 A3.4 A2.7 A
3 HP11 A10.6 A9.6 A4.8 A3.9 A
5 HP17.5 A16.7 A15.2 A7.6 A6.1 A
7.5 HP25.3 A24.2 A22 A11 A9 A
10 HP32.2 A30.8 A28 A14 A11 A
15 HP48.3 A46.2 A42 A21 A17 A
20 HP62.1 A59.4 A54 A27 A22 A
25 HP78.2 A74.8 A68 A34 A27 A
30 HP92 A88 A80 A40 A32 A
40 HP120 A114 A104 A52 A41 A
50 HP150 A143 A130 A65 A52 A
75 HP221 A211 A192 A96 A77 A
100 HP285 A273 A248 A124 A99 A

DC motors are not listed in this calculator. NEC 430.6(A)(3) requires using the motor nameplate full-load current with NEC Table 430.247 for DC branch-circuit sizing, so there is no general-purpose DC lookup that matches how the code actually works.

Related Calculators

Frequently Asked Questions

For the running current you will see on a meter, use Amps = (HP × 746) ÷ (Volts × Efficiency × Power Factor). One HP equals 746 watts of mechanical output; efficiency (typically 80-90%) and power factor (typically 0.80-0.85) both raise the electrical draw above that figure. For NEC branch-circuit conductor, switch, and OCP sizing, you should not use that calculated value. Per NEC 430.6(A)(1), motor branch circuits are sized from the full-load current in Table 430.248 (single-phase) or Table 430.250 (three-phase), which already incorporates typical efficiency and power factor.
A 1 HP single-phase motor at 120V draws about 8.6 A of running current at 85% efficiency and PF 0.85 (this is what the meter reads). For NEC branch-circuit sizing, the value you must use is the 16 A full-load current from NEC Table 430.248 (the 115V column covers 110-120V per 430.6(A)(1)). At 230V the table FLC drops to 8 A. These are different numbers used for different purposes and both show up on every result page.
Motor efficiency is the percentage of electrical power converted to mechanical power. A motor with 85% efficiency wastes 15% as heat, so a 1 HP motor with 746 W of mechanical output draws about 746 ÷ 0.85 = 878 W of electrical input at the terminals. Higher efficiency means lower running amps and lower electrical input for the same horsepower.
Squirrel-cage induction motors draw 5-7 times the NEC table full-load current for 2-5 seconds during startup (locked-rotor amps, or LRA). The exact multiplier is set by the NEMA code letter on the motor nameplate. This is why NEC 430.52(C)(1) allows motor branch-circuit OCP to be rated well above the running current. The percentage depends on the device type: inverse-time circuit breakers may go up to 250% of the table FLC, dual-element fuses up to 175%, instantaneous-trip breakers up to 800%, and non-time-delay fuses up to 300%. These are ceilings, not defaults.
Small motors (1/6 HP to 3/4 HP) are common in fans, pumps, furnace blowers, and power tools. A 1/2 HP single-phase motor at 120V has a calculated running current around 4-5 A but a NEC Table 430.248 FLC of 9.8 A, which is the number used for branch-circuit conductor and OCP sizing. Even though the motor draws less running current than a typical 15A household branch, sizing and overcurrent rules in Article 430 still apply.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.

Standards & References

This page cites the following electrical codes and standards. Always consult the current edition of your local adopted standard for authoritative requirements.

  1. NEC 430.6(A)(1). Motor full-load current values for general motor applications shall be taken from Tables 430.247 through 430.250 rather than the motor nameplate for the purposes of sizing conductors, switches, and overcurrent devices.
    National Electrical Code (NFPA 70), Article 430, Motors, Motor Circuits, and Controllers. Reference →
  2. NEC 430.52 and Table 430.52(C)(1). Motor branch-circuit short-circuit and ground-fault protection. Maximum ratings from Table 430.52(C)(1): non-time-delay fuse 300%, dual-element (time-delay) fuse 175%, instantaneous-trip breaker 800%, and inverse-time breaker 250% of full-load amps. The elevated percentages allow for motor locked-rotor startup current.
    National Electrical Code (NFPA 70), Article 430, Motors, Motor Circuits, and Controllers. Reference →
  3. NEC Table 310.16. Allowable ampacities of insulated conductors rated up to 2000V, 60°C through 90°C, not more than three current-carrying conductors in raceway or cable.
    National Electrical Code (NFPA 70), Article 310, Conductors for General Wiring. Reference →
  4. DOE 10 CFR Part 431. US Department of Energy energy conservation standards for electric motors. Sets minimum nominal full-load efficiencies for small, medium, and large electric motors sold in the US, including NEMA Premium and IE3/IE4 equivalents.
    US Department of Energy. Reference →
  5. NEMA MG 1. National standard for motors and generators. Defines motor efficiency classes, power factor values, insulation temperature ratings, service factor, and locked-rotor currents. The industry reference for motor nameplate interpretation.
    National Electrical Manufacturers Association. Reference →

Disclaimer: The information on this page is provided for reference. Always consult a licensed electrician and the current edition of your local adopted electrical code before performing electrical work.