kVA to Amps Calculator
Convert kilovolt-amps to amps at any voltage for generators, UPS systems, transformers, and commercial distribution equipment. Supports single-phase and three-phase (both line-to-line and line-to-neutral) so the residential split-phase and commercial three-phase answers land side by side.
What Is kVA?
kVA (kilovolt-amps) measures apparent power, the product of voltage and current in an AC circuit, which includes both real power (watts) and reactive power (VARs). The circuit's current draw, and therefore the sizing of conductors, breakers, and transformer windings, is set by the kVA figure regardless of the load's power factor. Generators, UPS systems, and distribution transformers publish a kVA rating for exactly this reason. They also publish a separate kW rating for the real-power side of the same hardware, and both ratings need to be checked independently when sizing a load against the source.
The Formulas
Single Phase
Used for residential and light commercial UPS systems, small generators, and single-phase transformers. The 1000 factor converts kVA to VA before dividing by the line voltage.
Three Phase
Used for commercial generators, UPS systems, and distribution transformers at 208V, 240V, or 480V. Unlike kW-to-amps, this formula does not include power factor because kVA already represents the total apparent power. The current is the same regardless of whether the load is resistive or reactive.
kVA vs kW (Load-Side vs Source-Side)
For a load, kW is the real power the load consumes (kW = kVA × load PF), and kVA is the apparent power the load pulls from the circuit. The relationship kW = kVA × Power Factor is a load-side conversion: it tells you how much real power a load with a given apparent power and power factor is drawing.
For a generator, UPS, or transformer, kW and kVA are two independent ratings set by the manufacturer, not two views of the same spec. A nameplate "10 kVA / 8 kW" means the alternator and winding are rated for 10 kVA of apparent power and the prime mover (engine, inverter, or core) is rated for 8 kW of real power. The kW rating is set by the engine or inverter design, not by multiplying kVA times an assumed power factor. Connect a PF 1.0 resistive load to a 10 kVA / 8 kW generator and the output still caps at 8 kW because the engine is the limiter; connect a PF 0.6 load and the output caps at 6 kW because the alternator current is the limiter. Always size a load against both the source's kVA rating and its kW rating independently, and check the manufacturer's spec sheet rather than inferring one from the other.
Unlike kW-to-amps conversion, kVA-to-amps does not involve power factor in the arithmetic because kVA already includes both real and reactive power. The circuit math is straightforward: Amps = (kVA × 1000) ÷ Volts for single-phase, and Amps = (kVA × 1000) ÷ (Volts × √3) for three-phase line-to-line.
Quick Results Table
Each cell uses the primary interpretation for its voltage so the table lines up with the result pages: residential 120/240V as single-phase, 230V as single-phase, commercial 208/400/480V as three-phase L-L per line. Click any cell to open the full breakdown for that kVA/voltage combination.
| kVA | 120V 1Φ | 208V 3Φ L-L | 230V 1Φ | 240V 1Φ | 400V 3Φ L-L | 480V 3Φ L-L |
|---|---|---|---|---|---|---|
| 1 kVA | 8.33A | 2.78A | 4.35A | 4.17A | 1.44A | 1.2A |
| 2 kVA | 16.67A | 5.55A | 8.7A | 8.33A | 2.89A | 2.41A |
| 5 kVA | 41.67A | 13.88A | 21.74A | 20.83A | 7.22A | 6.01A |
| 10 kVA | 83.33A | 27.76A | 43.48A | 41.67A | 14.43A | 12.03A |
| 15 kVA | 125A | 41.64A | 65.22A | 62.5A | 21.65A | 18.04A |
| 20 kVA | 166.67A | 55.51A | 86.96A | 83.33A | 28.87A | 24.06A |
| 25 kVA | 208.33A | 69.39A | 108.7A | 104.17A | 36.08A | 30.07A |
| 50 kVA | 416.67A | 138.79A | 217.39A | 208.33A | 72.17A | 60.14A |
| 75 kVA | 625A | 208.18A | 326.09A | 312.5A | 108.25A | 90.21A |
| 100 kVA | 833.33A | 277.57A | 434.78A | 416.67A | 144.34A | 120.28A |
Related Calculators
Frequently Asked Questions
Standards & References
This page cites the following electrical codes and standards. Always consult the current edition of your local adopted standard for authoritative requirements.
-
NEC Table 310.16.
Allowable ampacities of insulated conductors rated up to 2000V, 60°C through 90°C, not more than three current-carrying conductors in raceway or cable.
National Electrical Code (NFPA 70), Article 310, Conductors for General Wiring. Reference → -
NEC Article 450.
Transformers and transformer vaults: installation requirements, overcurrent protection, and ventilation for dry-type and liquid-filled transformers in the US.
National Electrical Code (NFPA 70). Reference → -
IEC 60076.
Power transformers: rating, construction, testing, and loading guidelines. International equivalent to IEEE C57 for oil-immersed and dry-type power transformers.
International Electrotechnical Commission. Reference → -
IEC 60038.
IEC standard voltages. Defines 230/400V as the nominal low-voltage supply for 50Hz systems, which harmonized European residential supply in 1995.
International Electrotechnical Commission. Reference → -
ANSI C84.1.
American National Standard for Electric Power Systems and Equipment: Voltage Ratings (60 Hz). Defines the nominal system voltages (120, 208, 240, 277, 480V) and their allowable ranges at the service entrance and utilization point.
American National Standards Institute / NEMA. Reference →
Disclaimer: The information on this page is provided for reference. Always consult a licensed electrician and the current edition of your local adopted electrical code before performing electrical work.