Voltage Drop Calculator
Calculate voltage drop for any wire gauge, current, and run length, and instantly check each run against NEC 210.19(A) Informational Note 4's 3% branch-circuit and 5% feeder+branch drop targets. Long runs need thicker wire to stay within the 3% target, and this tool shows exactly where that line sits.
Resistance values are copper conductors at the NEC Chapter 9 Table 8 75°C reference temperature. Aluminum has about 1.3 to 1.4 times the resistance of copper at the same temperature, so aluminum drop will be roughly that much higher for the same gauge; to compare aluminum explicitly, open any Wire Size Calculator page which picks copper and aluminum independently against the same drop target.
What Is Voltage Drop?
Voltage drop is the loss of voltage as electricity travels through a wire. Every conductor has resistance, and when current flows through that resistance, some voltage is consumed as heat. The longer the wire and the higher the current, the more voltage is lost before it reaches the load.
The Formulas
DC and Single-Phase AC
The "2" accounts for the round trip: current travels out to the load on one conductor and returns on another. This formula applies to DC circuits and single-phase AC (120V, 240V residential branches).
Three-Phase AC
Three-phase systems (208V, 480V commercial / industrial) use the √3 factor rather than a round-trip of 2. The balanced three-conductor geometry means the line-to-line voltage drop is proportional to √3 times the one-way IR product, not twice it. Using the 1-phase formula on a 3-phase circuit overstates the drop by about 15%.
Resistance is the wire's ohms per 1000 feet (see the gauge table below). To get the percentage, divide the drop by the source voltage and multiply by 100.
NEC Drop Targets
NEC 210.19(A) Informational Note 4 cites performance-recommendation targets for branch-circuit and feeder+branch voltage drop:
| Circuit Type | Drop Target | At 120V | At 240V |
|---|---|---|---|
| Branch circuit | ≤ 3% | ≤ 3.6V | ≤ 7.2V |
| Feeder + branch total | ≤ 5% | ≤ 6.0V | ≤ 12.0V |
These are performance recommendations, not hard code requirements. Sitting past them typically shows up as motors running hotter and starting slower, incandescent and halogen lighting dimming, and sensitive electronics operating at the low end of their input tolerance, rather than a code violation on its own.
Three Factors That Affect Voltage Drop
- Wire gauge: Thicker wire (lower AWG) has less resistance. Doubling the cross-sectional area roughly halves the voltage drop.
- Current: More amps means more drop. Voltage drop is directly proportional to current.
- Distance: Longer runs mean more resistance. Voltage drop is directly proportional to distance.
You can reduce voltage drop by using thicker wire, shortening the run, or (where possible) increasing the circuit voltage from 120V to 240V.
Wire Gauge Reference
| Gauge | Resistance (Ω/1000ft) | Ampacity (60°C) | Ampacity (75°C) | NEC Branch OCP |
|---|---|---|---|---|
| 14 AWG | 3.14 | 15A | 20A | 15A (240.4D) |
| 12 AWG | 1.98 | 20A | 25A | 20A (240.4D) |
| 10 AWG | 1.24 | 30A | 35A | 30A (240.4D) |
| 8 AWG | 0.778 | 40A | 50A | 50A |
| 6 AWG | 0.491 | 55A | 65A | 65A |
| 4 AWG | 0.308 | 70A | 85A | 85A |
| 3 AWG | 0.245 | 85A | 100A | 100A |
| 2 AWG | 0.194 | 95A | 115A | 115A |
| 1 AWG | 0.154 | 110A | 130A | 130A |
| 1/0 AWG | 0.122 | 125A | 150A | 150A |
| 2/0 AWG | 0.0967 | 145A | 175A | 175A |
| 3/0 AWG | 0.0766 | 165A | 200A | 200A |
| 4/0 AWG | 0.0608 | 195A | 230A | 230A |
| 250 kcmil | 0.0515 | 215A | 255A | 255A |
| 300 kcmil | 0.0429 | 240A | 285A | 285A |
| 350 kcmil | 0.0367 | 260A | 310A | 310A |
| 500 kcmil | 0.0258 | 320A | 380A | 380A |
| 750 kcmil | 0.0171 | 400A | 475A | 475A |
NEC Branch OCP is the branch-circuit overcurrent cap for that conductor. For 14, 12, and 10 AWG copper, NEC 240.4(D) caps the breaker below the raw 75°C ampacity (the "small conductor rule"). Larger gauges follow the standard ampacity table.
Related Calculators
Frequently Asked Questions
Standards & References
This page cites the following electrical codes and standards. Always consult the current edition of your local adopted standard for authoritative requirements.
-
NEC 210.19(A) Informational Note 4.
Branch-circuit conductors sized to prevent a voltage drop exceeding 3% at the farthest outlet. Combined with feeders, total voltage drop should not exceed 5%.
National Electrical Code (NFPA 70), Article 210, Branch Circuits. Reference → -
NEC 215.2(A)(1) Informational Note 2.
Feeder conductors sized to prevent a voltage drop exceeding 3%. Total branch + feeder drop should not exceed 5%.
National Electrical Code (NFPA 70), Article 215, Feeders. Reference → -
NEC Table 310.16.
Allowable ampacities of insulated conductors rated up to 2000V, 60°C through 90°C, not more than three current-carrying conductors in raceway or cable.
National Electrical Code (NFPA 70), Article 310, Conductors for General Wiring. Reference → -
IEC 60364.
Low-voltage electrical installations. The international counterpart to the NEC, covering voltages up to 1000V AC / 1500V DC in residential, commercial, and industrial installations.
International Electrotechnical Commission. Reference →
Disclaimer: The information on this page is provided for reference. Always consult a licensed electrician and the current edition of your local adopted electrical code before performing electrical work.