How Many Amps Does a 2 HP three-phase Motor Draw at 208V?

A 2 HP three-phase motor at 208V draws approximately 5.73 amps per line during normal operation (85% efficiency, PF 0.85). Startup current can be 5-7 times the NEC Table 430.250 FLC (37.5-52.5 A) for a few seconds, which affects breaker and wire sizing.

Common applications for 2 HP motors: commercial HVAC fans, rooftop-unit blowers, pump motors, three-phase industrial equipment.

2 HP three-phase motor at 208V
5.73 Amps per line running
Calculated running current at the motor terminals at the assumed 85% efficiency and PF 0.85, per line on a balanced three-phase circuit. This is a conversion from the nameplate horsepower using those assumptions, not a measured value; a real meter reading depends on the motor's actual nameplate efficiency, loading, temperature, and motor design.
NEC Table 430.250 FLC (code sizing base)7.5 A
Conductor min ampacity (NEC 430.22, 125% of FLC)9.38 A
Electrical input (HP × 746 ÷ efficiency)1,755.29 W
5.73
7.5

Use the running amps for metering and energy calculations. For branch-circuit sizing, AC motors use the NEC Table 430.248 / 430.250 full-load current under NEC 430.6(A)(1); DC motors use the motor nameplate full-load current under NEC 430.6(A)(3), with Table 430.247 as the reference. Three-phase current is shown per line on a balanced circuit.

Formula (three-phase)

I(A) = (HP × 746) ÷ (√3 × VL-L × Eff × PF)

(2 × 746) ÷ (√3 × 208 × 0.85 × 0.85) = 1,492 ÷ 260.29 = 5.73 A per line
  1. Convert HP to watts: 2 × 746 = 1,492W
  2. Denominator: √3 × 208 × 0.85 × 0.85 = 1.73 × 208 × 0.85 × 0.85 = 260.29
  3. Result: 1,492 ÷ 260.29 = 5.73 amps per line

Three-phase current is per line on a balanced circuit. Voltage is line-to-line; the √3 factor comes from the three-phase vector geometry, not a round-trip doubling.

NEC Reference Values

This section lists the Code reference numbers a motor branch circuit is sized from. Final conductor, breaker, disconnect, and overload selection is an install decision a licensed electrician makes against the motor nameplate, the actual install conditions, and the applicable NEC articles, not a decision a conversion page can make for you.

NEC Sizing Base: NEC Table 430.250 FLC

Per NEC 430.6(A)(1), motor branch-circuit conductors, switches, and overcurrent protection are sized from the values in Table 430.248 (single-phase) or Table 430.250 (three-phase), not from the motor nameplate and not from a calculated full-load amps. For a 2 HP three-phase motor at 208V, the table value is 7.5 A (direct column match under 430.6(A)(1)).

The 5.73 A shown in the hero is the calculated running current at 85% efficiency and PF 0.85, per line on a balanced three-phase circuit. This is a conversion from the nameplate horsepower under those assumptions, not a measured value; a real meter reading depends on the motor's actual efficiency, loading, temperature, and design. Use this figure for energy and metering estimates, and use 7.5 A as the reference FLC when an electrician walks through NEC 430 against the nameplate.

NEC 430.22 Conductor Rule (reference formula)

NEC 430.22 requires motor branch-circuit conductor ampacity of at least 125% of the Code sizing FLC. As a reference calculation against the NEC Table 430.250 value: 7.5 × 1.25 = 9.38 A. The selected conductor is taken from NEC Table 310.16 at the applicable termination temperature column, with ambient, bundling, and cable-type adjustments applied by the installer. Motor branch-circuit conductors are exempt from the 240.4(D) small-conductor rule via 240.4(G).

NEC 430.52 Overcurrent Protection (code caps)

NEC Table 430.52(C)(1) gives the maximum rating for motor short-circuit and ground-fault protection as a percentage of the Code sizing FLC. The percentage depends on the device type:

Device TypeMaximum % of Table FLC (430.52(C)(1))
Non-time-delay fuse300%
Dual-element (time-delay) fuse175%
Inverse-time circuit breaker250%
Instantaneous-trip circuit breaker800%

These percentages are maximum caps, not install picks. A real circuit applies the percentage against the Code sizing FLC for the specific device type, rounds up to a standard size per 430.52(C)(1)(a), and is verified against the motor nameplate and the install conditions by the installer. The elevated percentages exist so short-circuit protection does not nuisance-trip on locked-rotor startup inrush.

Locked Rotor (Startup) Current

During the first 2-5 seconds of startup, a squirrel-cage induction motor typically draws 5 to 7 times the NEC Table 430.250 FLC of 7.5 A (roughly 37.5 to 52.5 A). This is why the 430.52(C)(1) percentages above are so much higher than running current: the short-circuit/ground-fault protective device has to ride through locked-rotor inrush without tripping. Actual LRA is set by the motor's NEMA code letter on the nameplate and should be checked there for a real install.

CurrentAmpsDuration
Calculated running current (meter)5.73 A per lineContinuous at full load
NEC Table 430.250 FLC (Code reference)7.5 ASizing base, not metered
Locked rotor (typical, 5-7×)37.5-52.5 A2-5 seconds

Operating Cost

Motor mechanical output is 1,492 W (2 HP × 746). Electrical input at the terminals is higher because no motor is 100% efficient: 1,492 ÷ 0.85 = 1,755.29 W. At $0.17/kWh, running cost is $0.30/hour or $71.62/month at 8 hours/day. Full breakdown at 1,755.29 W.

Amps by Motor Efficiency (three-phase)

Motor efficiency directly affects amp draw. A more efficient motor draws less current for the same HP output. Values below are the calculated three-phase running current at 208V per line and PF 0.85:

EfficiencyAmps at 208V (per line)Watts ConsumedWaste Heat
75%6.5 A1,989.33 W497.33 W
80%6.09 A1,865 W373 W
85%5.73 A1,755.29 W263.29 W
90%5.41 A1,657.78 W165.78 W
95%5.13 A1,570.53 W78.53 W

Other HP Values at 208V (three-phase)

Running current is the calculated three-phase draw per line at 85% efficiency and 0.85 PF (a conversion from HP under those assumptions, not a measured value). NEC Table FLC is the value from NEC Table 430.250 used for branch-circuit conductor and OCP sizing under NEC 430.6(A)(1). LRA is estimated at 5-7× the NEC table FLC; rows outside the table show n/a because there is no code-authoritative LRA basis for that HP/voltage/phase combination. Row links open each result page in three-phase mode.

HPRunning Amps
(calculated)
NEC Table 430.250 FLCLRA Estimate
(5-7× FLC)
1/8 HP0.3583 Aoff-tablen/a
1/6 HP0.4778 Aoff-tablen/a
1/4 HP0.7165 Aoff-tablen/a
1/3 HP0.9552 Aoff-tablen/a
1/2 HP1.43 A2.4 A12-16.8 A
3/4 HP2.15 A3.5 A17.5-24.5 A
1 HP2.87 A4.6 A23-32.2 A
1.5 HP4.3 A6.6 A33-46.2 A
2 HP5.73 A7.5 A37.5-52.5 A
3 HP8.6 A10.6 A53-74.2 A
5 HP14.33 A16.7 A83.5-116.9 A
7.5 HP21.5 A24.2 A121-169.4 A
10 HP28.66 A30.8 A154-215.6 A
15 HP42.99 A46.2 A231-323.4 A
20 HP57.32 A59.4 A297-415.8 A
25 HP71.65 A74.8 A374-523.6 A
30 HP85.98 A88 A440-616 A
40 HP114.64 A114 A570-798 A
50 HP143.3 A143 A715-1,001 A
75 HP214.95 A211 A1,055-1,477 A

Frequently Asked Questions

At the terminals, a 2 HP three-phase motor at 208V draws about 5.73 amps per line at 85% efficiency and 0.85 power factor. For NEC branch-circuit sizing use the NEC Table 430.250 full-load current instead: 7.5 A.
NEC Table 430.52(C)(1) gives the maximum OCP rating as a percentage of the NEC Table 430.250 FLC. The ceilings by device type are 300% for non-time-delay fuses, 175% for dual-element (time-delay) fuses, 250% for inverse-time circuit breakers, and 800% for instantaneous-trip breakers. These percentages are ceilings, not starting points, and 250% is not a blanket motor rule. The actual max for a specific install comes from picking the device type, applying the matching percentage to the 7.5 A NEC Table 430.250 FLC, rounding up to a standard size per 430.52(C)(1)(a), and verifying against the motor startup profile.
Operating cost is based on electrical input, not mechanical HP output. At 85% efficiency, a 2 HP motor draws about 1,755.29 W at the terminals. At $0.17/kWh (US residential average, last reviewed April 2026), that is $0.30/hour or $71.62/month at 8 hours/day.
2 HP equals 1,492 watts of mechanical output (1 HP = 746 W). The electrical input at the terminals is higher because no motor is 100% efficient: at 85% efficiency the input is about 1,755.29 W.
Locked-rotor (startup) current typically runs 5-7 times the NEC Table 430.250 FLC for a squirrel-cage induction motor: 37.5-52.5 A for 2-5 seconds. The exact value depends on the NEMA code letter stamped on the motor nameplate.
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.