2/0 AWG Voltage Drop Chart

2/0 AWG copper wire has a resistance of 0.0967 ohms per 1000 feet. NEC 240.4(D) and the standard ampacity tables cap this gauge at 175A for a branch-circuit breaker (60°C ampacity: 145A; 75°C: 175A). At 100 feet on a 120V circuit, it stays under 3% voltage drop up to about 186A.

2/0 AWG Wire Specifications

PropertyValue
Gauge2/0 AWG
Resistance (copper)0.0967 Ω per 1000ft
Ampacity (60°C)145A
Ampacity (75°C)175A
NEC branch-circuit OCP175A
Amps that land on 3% drop at 100ft (120V)~186A

Voltage Drop by Amps & Distance (120V)

Green = within the 3% branch-circuit drop target, Amber = 3-5% (past branch target, within 5% feeder+branch total), Red = past the 5% feeder+branch total recommendation

When to Use 2/0 AWG

Typical applications: Main service entrance, large commercial feeders, and industrial applications.

Under typical 75°C-termination assumptions, 2/0 AWG is commonly protected by up to 175A branch-circuit OCP. Real install ceilings depend on conductor and termination temperature ratings, cable type (NM-B is limited to the 60°C column in residential use, so the usable value is lower), NEC 310.15(C)(1) bundling adjustments, and NEC 310.15(B) ambient corrections. Even with ampacity margin, longer runs may fall outside the 3% branch-circuit drop target recommended in NEC 210.19(A) Informational Note 4, which is why the distance table above matters.

Compared to Adjacent Gauges

GaugeResistanceAmpacity (75°C)Drop at 20A/100ft (120V)
1/0 AWG (thinner)0.122 Ω/kft150A0.4067%
2/0 AWG0.0967 Ω/kft175A0.3223%
3/0 AWG (thicker)0.0766 Ω/kft200A0.2553%