Wire Size for 0.21 Amps

Typical copper wire gauges for 0.21 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 0.21A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

0.21A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.033V (0.0275%) check_circle OK
50 ft 14 AWG 0.0659V (0.055%) check_circle OK
75 ft 14 AWG 0.0989V (0.0824%) check_circle OK
100 ft 14 AWG 0.1319V (0.1099%) check_circle OK
125 ft 14 AWG 0.1649V (0.1374%) check_circle OK
150 ft 14 AWG 0.1978V (0.1649%) check_circle OK
175 ft 14 AWG 0.2308V (0.1923%) check_circle OK
200 ft 14 AWG 0.2638V (0.2198%) check_circle OK
250 ft 14 AWG 0.3297V (0.2748%) check_circle OK
300 ft 14 AWG 0.3956V (0.3297%) check_circle OK
400 ft 14 AWG 0.5275V (0.4396%) check_circle OK
500 ft 14 AWG 0.6594V (0.5495%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.