Wire Size for 0.82 Amps

Typical copper wire gauges for 0.82 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 0.82A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

0.82A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.1287V (0.1073%) check_circle OK
50 ft 14 AWG 0.2575V (0.2146%) check_circle OK
75 ft 14 AWG 0.3862V (0.3218%) check_circle OK
100 ft 14 AWG 0.515V (0.4291%) check_circle OK
125 ft 14 AWG 0.6437V (0.5364%) check_circle OK
150 ft 14 AWG 0.7724V (0.6437%) check_circle OK
175 ft 14 AWG 0.9012V (0.751%) check_circle OK
200 ft 14 AWG 1.03V (0.8583%) check_circle OK
250 ft 14 AWG 1.29V (1.07%) check_circle OK
300 ft 14 AWG 1.54V (1.29%) check_circle OK
400 ft 14 AWG 2.06V (1.72%) check_circle OK
500 ft 14 AWG 2.57V (2.15%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.