Wire Size for 0.84 Amps
Typical copper wire gauges for 0.84 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 0.84A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.
0.84A Wire Gauge by Distance
| Distance | Copper Gauge | V-Drop (Cu) | NEC Status |
|---|---|---|---|
| 25 ft | 14 AWG | 0.1319V (0.1099%) | OK |
| 50 ft | 14 AWG | 0.2638V (0.2198%) | OK |
| 75 ft | 14 AWG | 0.3956V (0.3297%) | OK |
| 100 ft | 14 AWG | 0.5275V (0.4396%) | OK |
| 125 ft | 14 AWG | 0.6594V (0.5495%) | OK |
| 150 ft | 14 AWG | 0.7913V (0.6594%) | OK |
| 175 ft | 14 AWG | 0.9232V (0.7693%) | OK |
| 200 ft | 14 AWG | 1.06V (0.8792%) | OK |
| 250 ft | 14 AWG | 1.32V (1.1%) | OK |
| 300 ft | 14 AWG | 1.58V (1.32%) | OK |
| 400 ft | 14 AWG | 2.11V (1.76%) | OK |
| 500 ft | 14 AWG | 2.64V (2.2%) | OK |
Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.
Also Calculate
Other Amperages
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.