Wire Size for 0.8 Amps

Typical copper wire gauges for 0.8 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 0.8A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

0.8A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.1256V (0.1047%) check_circle OK
50 ft 14 AWG 0.2512V (0.2093%) check_circle OK
75 ft 14 AWG 0.3768V (0.314%) check_circle OK
100 ft 14 AWG 0.5024V (0.4187%) check_circle OK
125 ft 14 AWG 0.628V (0.5233%) check_circle OK
150 ft 14 AWG 0.7536V (0.628%) check_circle OK
175 ft 14 AWG 0.8792V (0.7327%) check_circle OK
200 ft 14 AWG 1V (0.8373%) check_circle OK
250 ft 14 AWG 1.26V (1.05%) check_circle OK
300 ft 14 AWG 1.51V (1.26%) check_circle OK
400 ft 14 AWG 2.01V (1.67%) check_circle OK
500 ft 14 AWG 2.51V (2.09%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.