Wire Size for 1.15 Amps

Typical copper wire gauges for 1.15 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 1.15A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

1.15A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.1806V (0.1505%) check_circle OK
50 ft 14 AWG 0.3611V (0.3009%) check_circle OK
75 ft 14 AWG 0.5417V (0.4514%) check_circle OK
100 ft 14 AWG 0.7222V (0.6018%) check_circle OK
125 ft 14 AWG 0.9028V (0.7523%) check_circle OK
150 ft 14 AWG 1.08V (0.9027%) check_circle OK
175 ft 14 AWG 1.26V (1.05%) check_circle OK
200 ft 14 AWG 1.44V (1.2%) check_circle OK
250 ft 14 AWG 1.81V (1.5%) check_circle OK
300 ft 14 AWG 2.17V (1.81%) check_circle OK
400 ft 14 AWG 2.89V (2.41%) check_circle OK
500 ft 12 AWG 2.28V (1.9%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.