Wire Size for 1.18 Amps

Typical copper wire gauges for 1.18 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 1.18A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

1.18A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.1853V (0.1544%) check_circle OK
50 ft 14 AWG 0.3705V (0.3088%) check_circle OK
75 ft 14 AWG 0.5558V (0.4631%) check_circle OK
100 ft 14 AWG 0.741V (0.6175%) check_circle OK
125 ft 14 AWG 0.9263V (0.7719%) check_circle OK
150 ft 14 AWG 1.11V (0.9263%) check_circle OK
175 ft 14 AWG 1.3V (1.08%) check_circle OK
200 ft 14 AWG 1.48V (1.24%) check_circle OK
250 ft 14 AWG 1.85V (1.54%) check_circle OK
300 ft 14 AWG 2.22V (1.85%) check_circle OK
400 ft 14 AWG 2.96V (2.47%) check_circle OK
500 ft 12 AWG 2.34V (1.95%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.