Wire Size for 1.23 Amps

Typical copper wire gauges for 1.23 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 1.23A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

1.23A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.1931V (0.1609%) check_circle OK
50 ft 14 AWG 0.3862V (0.3219%) check_circle OK
75 ft 14 AWG 0.5793V (0.4828%) check_circle OK
100 ft 14 AWG 0.7724V (0.6437%) check_circle OK
125 ft 14 AWG 0.9656V (0.8046%) check_circle OK
150 ft 14 AWG 1.16V (0.9656%) check_circle OK
175 ft 14 AWG 1.35V (1.13%) check_circle OK
200 ft 14 AWG 1.54V (1.29%) check_circle OK
250 ft 14 AWG 1.93V (1.61%) check_circle OK
300 ft 14 AWG 2.32V (1.93%) check_circle OK
400 ft 14 AWG 3.09V (2.57%) check_circle OK
500 ft 12 AWG 2.44V (2.03%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.