Wire Size for 1.38 Amps
Typical copper wire gauges for 1.38 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 1.38A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.
1.38A Wire Gauge by Distance
| Distance | Copper Gauge | V-Drop (Cu) | NEC Status |
|---|---|---|---|
| 25 ft | 14 AWG | 0.2167V (0.1806%) | OK |
| 50 ft | 14 AWG | 0.4333V (0.3611%) | OK |
| 75 ft | 14 AWG | 0.65V (0.5417%) | OK |
| 100 ft | 14 AWG | 0.8666V (0.7222%) | OK |
| 125 ft | 14 AWG | 1.08V (0.9027%) | OK |
| 150 ft | 14 AWG | 1.3V (1.08%) | OK |
| 175 ft | 14 AWG | 1.52V (1.26%) | OK |
| 200 ft | 14 AWG | 1.73V (1.44%) | OK |
| 250 ft | 14 AWG | 2.17V (1.81%) | OK |
| 300 ft | 14 AWG | 2.6V (2.17%) | OK |
| 400 ft | 14 AWG | 3.47V (2.89%) | OK |
| 500 ft | 12 AWG | 2.73V (2.28%) | OK |
Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.
Also Calculate
Other Amperages
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.