Wire Size for 1.74 Amps

Typical copper wire gauges for 1.74 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 1.74A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

1.74A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.2732V (0.2277%) check_circle OK
50 ft 14 AWG 0.5464V (0.4553%) check_circle OK
75 ft 14 AWG 0.8195V (0.683%) check_circle OK
100 ft 14 AWG 1.09V (0.9106%) check_circle OK
125 ft 14 AWG 1.37V (1.14%) check_circle OK
150 ft 14 AWG 1.64V (1.37%) check_circle OK
175 ft 14 AWG 1.91V (1.59%) check_circle OK
200 ft 14 AWG 2.19V (1.82%) check_circle OK
250 ft 14 AWG 2.73V (2.28%) check_circle OK
300 ft 14 AWG 3.28V (2.73%) check_circle OK
400 ft 12 AWG 2.76V (2.3%) check_circle OK
500 ft 12 AWG 3.45V (2.87%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.