Wire Size for 1.83 Amps

Typical copper wire gauges for 1.83 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 1.83A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

1.83A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.2873V (0.2394%) check_circle OK
50 ft 14 AWG 0.5746V (0.4789%) check_circle OK
75 ft 14 AWG 0.8619V (0.7183%) check_circle OK
100 ft 14 AWG 1.15V (0.9577%) check_circle OK
125 ft 14 AWG 1.44V (1.2%) check_circle OK
150 ft 14 AWG 1.72V (1.44%) check_circle OK
175 ft 14 AWG 2.01V (1.68%) check_circle OK
200 ft 14 AWG 2.3V (1.92%) check_circle OK
250 ft 14 AWG 2.87V (2.39%) check_circle OK
300 ft 14 AWG 3.45V (2.87%) check_circle OK
400 ft 12 AWG 2.9V (2.42%) check_circle OK
500 ft 10 AWG 2.27V (1.89%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.