Wire Size for 10.91 Amps
Typical copper wire gauges for 10.91 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 10.91A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.
10.91A Wire Gauge by Distance
| Distance | Copper Gauge | V-Drop (Cu) | NEC Status |
|---|---|---|---|
| 25 ft | 14 AWG | 1.71V (1.43%) | OK |
| 50 ft | 14 AWG | 3.43V (2.85%) | OK |
| 75 ft | 12 AWG | 3.24V (2.7%) | OK |
| 100 ft | 10 AWG | 2.71V (2.25%) | OK |
| 125 ft | 10 AWG | 3.38V (2.82%) | OK |
| 150 ft | 8 AWG | 2.55V (2.12%) | OK |
| 175 ft | 8 AWG | 2.97V (2.48%) | OK |
| 200 ft | 8 AWG | 3.4V (2.83%) | OK |
| 250 ft | 6 AWG | 2.68V (2.23%) | OK |
| 300 ft | 6 AWG | 3.21V (2.68%) | OK |
| 400 ft | 4 AWG | 2.69V (2.24%) | OK |
| 500 ft | 4 AWG | 3.36V (2.8%) | OK |
Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.