Wire Size for 104.55 Amps

Typical copper and aluminum wire gauges for 104.55 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

104.55A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 2 AWG 1/0 AWG 1.01V (0.8451%) check_circle OK
50 ft 2 AWG 1/0 AWG 2.03V (1.69%) check_circle OK
75 ft 2 AWG 1/0 AWG 3.04V (2.54%) check_circle OK
100 ft 1 AWG 1/0 AWG 3.22V (2.68%) check_circle OK
125 ft 1/0 AWG 2/0 AWG 3.19V (2.66%) check_circle OK
150 ft 2/0 AWG 3/0 AWG 3.03V (2.53%) check_circle OK
175 ft 2/0 AWG 4/0 AWG 3.54V (2.95%) check_circle OK
200 ft 3/0 AWG 4/0 AWG 3.2V (2.67%) check_circle OK
250 ft 4/0 AWG 350 kcmil 3.18V (2.65%) check_circle OK
300 ft 250 kcmil 500 kcmil 3.23V (2.69%) check_circle OK
400 ft 300 kcmil 500 kcmil 3.59V (2.99%) check_circle OK
500 ft 500 kcmil 750 kcmil 2.7V (2.25%) check_circle OK

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.