Wire Size for 11.55 Amps

Typical copper wire gauges for 11.55 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 11.55A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

11.55A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 1.81V (1.51%) check_circle OK
50 ft 12 AWG 2.29V (1.91%) check_circle OK
75 ft 12 AWG 3.43V (2.86%) check_circle OK
100 ft 10 AWG 2.86V (2.39%) check_circle OK
125 ft 10 AWG 3.58V (2.98%) check_circle OK
150 ft 8 AWG 2.7V (2.25%) check_circle OK
175 ft 8 AWG 3.15V (2.62%) check_circle OK
200 ft 8 AWG 3.59V (3%) check_circle OK
250 ft 6 AWG 2.84V (2.36%) check_circle OK
300 ft 6 AWG 3.4V (2.84%) check_circle OK
400 ft 4 AWG 2.85V (2.37%) check_circle OK
500 ft 4 AWG 3.56V (2.96%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.