Wire Size for 11.59 Amps

Typical copper wire gauges for 11.59 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 11.59A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

11.59A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 1.82V (1.52%) check_circle OK
50 ft 12 AWG 2.29V (1.91%) check_circle OK
75 ft 12 AWG 3.44V (2.87%) check_circle OK
100 ft 10 AWG 2.87V (2.4%) check_circle OK
125 ft 10 AWG 3.59V (2.99%) check_circle OK
150 ft 8 AWG 2.71V (2.25%) check_circle OK
175 ft 8 AWG 3.16V (2.63%) check_circle OK
200 ft 6 AWG 2.28V (1.9%) check_circle OK
250 ft 6 AWG 2.85V (2.37%) check_circle OK
300 ft 6 AWG 3.41V (2.85%) check_circle OK
400 ft 4 AWG 2.86V (2.38%) check_circle OK
500 ft 4 AWG 3.57V (2.97%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.