Wire Size for 112.5 Amps

Typical copper and aluminum wire gauges for 112.5 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

112.5A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 2 AWG 1/0 AWG 1.09V (0.9094%) check_circle OK
50 ft 2 AWG 1/0 AWG 2.18V (1.82%) check_circle OK
75 ft 2 AWG 1/0 AWG 3.27V (2.73%) check_circle OK
100 ft 1 AWG 2/0 AWG 3.47V (2.89%) check_circle OK
125 ft 1/0 AWG 3/0 AWG 3.43V (2.86%) check_circle OK
150 ft 2/0 AWG 3/0 AWG 3.26V (2.72%) check_circle OK
175 ft 3/0 AWG 4/0 AWG 3.02V (2.51%) check_circle OK
200 ft 3/0 AWG 300 kcmil 3.45V (2.87%) check_circle OK
250 ft 4/0 AWG 350 kcmil 3.42V (2.85%) check_circle OK
300 ft 250 kcmil 500 kcmil 3.48V (2.9%) check_circle OK
400 ft 350 kcmil 750 kcmil 3.3V (2.75%) check_circle OK
500 ft 500 kcmil 750 kcmil 2.9V (2.42%) check_circle OK

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.