Wire Size for 113.64 Amps

Typical copper and aluminum wire gauges for 113.64 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

113.64A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 2 AWG 1/0 AWG 1.1V (0.9186%) check_circle OK
50 ft 2 AWG 1/0 AWG 2.2V (1.84%) check_circle OK
75 ft 2 AWG 1/0 AWG 3.31V (2.76%) check_circle OK
100 ft 1 AWG 2/0 AWG 3.5V (2.92%) check_circle OK
125 ft 1/0 AWG 3/0 AWG 3.47V (2.89%) check_circle OK
150 ft 2/0 AWG 3/0 AWG 3.3V (2.75%) check_circle OK
175 ft 3/0 AWG 4/0 AWG 3.05V (2.54%) check_circle OK
200 ft 3/0 AWG 300 kcmil 3.48V (2.9%) check_circle OK
250 ft 4/0 AWG 350 kcmil 3.45V (2.88%) check_circle OK
300 ft 250 kcmil 500 kcmil 3.51V (2.93%) check_circle OK
400 ft 350 kcmil 750 kcmil 3.34V (2.78%) check_circle OK
500 ft 500 kcmil 750 kcmil 2.93V (2.44%) check_circle OK

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.