Wire Size for 115.83 Amps

Typical copper and aluminum wire gauges for 115.83 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

115.83A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 1 AWG 1/0 AWG 0.8919V (0.7432%) check_circle OK
50 ft 1 AWG 1/0 AWG 1.78V (1.49%) check_circle OK
75 ft 1 AWG 1/0 AWG 2.68V (2.23%) check_circle OK
100 ft 1 AWG 2/0 AWG 3.57V (2.97%) check_circle OK
125 ft 1/0 AWG 3/0 AWG 3.53V (2.94%) check_circle OK
150 ft 2/0 AWG 3/0 AWG 3.36V (2.8%) check_circle OK
175 ft 3/0 AWG 4/0 AWG 3.11V (2.59%) check_circle OK
200 ft 3/0 AWG 300 kcmil 3.55V (2.96%) check_circle OK
250 ft 4/0 AWG 350 kcmil 3.52V (2.93%) check_circle OK
300 ft 250 kcmil 500 kcmil 3.58V (2.98%) check_circle OK
400 ft 350 kcmil 750 kcmil 3.4V (2.83%) check_circle OK
500 ft 500 kcmil 750 kcmil 2.99V (2.49%) check_circle OK

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.