Wire Size for 122.67 Amps

Typical copper and aluminum wire gauges for 122.67 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

122.67A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 1 AWG 2/0 AWG 0.9446V (0.7871%) check_circle OK
50 ft 1 AWG 2/0 AWG 1.89V (1.57%) check_circle OK
75 ft 1 AWG 2/0 AWG 2.83V (2.36%) check_circle OK
100 ft 1/0 AWG 2/0 AWG 2.99V (2.49%) check_circle OK
125 ft 2/0 AWG 3/0 AWG 2.97V (2.47%) check_circle OK
150 ft 2/0 AWG 4/0 AWG 3.56V (2.97%) check_circle OK
175 ft 3/0 AWG 4/0 AWG 3.29V (2.74%) check_circle OK
200 ft 4/0 AWG 300 kcmil 2.98V (2.49%) check_circle OK
250 ft 250 kcmil 500 kcmil 3.16V (2.63%) check_circle OK
300 ft 300 kcmil 500 kcmil 3.16V (2.63%) check_circle OK
400 ft 500 kcmil 750 kcmil 2.53V (2.11%) check_circle OK
500 ft 500 kcmil 750 kcmil 3.16V (2.64%) check_circle OK

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.