Wire Size for 13.06 Amps

Typical copper wire gauges for 13.06 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 13.06A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

13.06A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 2.05V (1.71%) check_circle OK
50 ft 12 AWG 2.59V (2.15%) check_circle OK
75 ft 10 AWG 2.43V (2.02%) check_circle OK
100 ft 10 AWG 3.24V (2.7%) check_circle OK
125 ft 8 AWG 2.54V (2.12%) check_circle OK
150 ft 8 AWG 3.05V (2.54%) check_circle OK
175 ft 8 AWG 3.56V (2.96%) check_circle OK
200 ft 6 AWG 2.56V (2.14%) check_circle OK
250 ft 6 AWG 3.21V (2.67%) check_circle OK
300 ft 4 AWG 2.41V (2.01%) check_circle OK
400 ft 4 AWG 3.22V (2.68%) check_circle OK
500 ft 3 AWG 3.2V (2.67%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.