Wire Size for 13.58 Amps

Typical copper wire gauges for 13.58 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 13.58A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

13.58A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 2.13V (1.78%) check_circle OK
50 ft 12 AWG 2.69V (2.24%) check_circle OK
75 ft 10 AWG 2.53V (2.1%) check_circle OK
100 ft 10 AWG 3.37V (2.81%) check_circle OK
125 ft 8 AWG 2.64V (2.2%) check_circle OK
150 ft 8 AWG 3.17V (2.64%) check_circle OK
175 ft 6 AWG 2.33V (1.94%) check_circle OK
200 ft 6 AWG 2.67V (2.22%) check_circle OK
250 ft 6 AWG 3.33V (2.78%) check_circle OK
300 ft 4 AWG 2.51V (2.09%) check_circle OK
400 ft 4 AWG 3.35V (2.79%) check_circle OK
500 ft 3 AWG 3.33V (2.77%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.