Wire Size for 133.33 Amps

Typical copper and aluminum wire gauges for 133.33 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

133.33A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 1/0 AWG 2/0 AWG 0.8133V (0.6778%) check_circle OK
50 ft 1/0 AWG 2/0 AWG 1.63V (1.36%) check_circle OK
75 ft 1/0 AWG 2/0 AWG 2.44V (2.03%) check_circle OK
100 ft 1/0 AWG 2/0 AWG 3.25V (2.71%) check_circle OK
125 ft 2/0 AWG 3/0 AWG 3.22V (2.69%) check_circle OK
150 ft 3/0 AWG 4/0 AWG 3.06V (2.55%) check_circle OK
175 ft 3/0 AWG 300 kcmil 3.57V (2.98%) check_circle OK
200 ft 4/0 AWG 350 kcmil 3.24V (2.7%) check_circle OK
250 ft 250 kcmil 500 kcmil 3.43V (2.86%) check_circle OK
300 ft 300 kcmil 500 kcmil 3.43V (2.86%) check_circle OK
400 ft 500 kcmil 750 kcmil 2.75V (2.29%) check_circle OK
500 ft 500 kcmil no aluminum pick 3.44V (2.87%) check_circle OK

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.