Wire Size for 14.87 Amps

Typical copper wire gauges for 14.87 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 14.87A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

14.87A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 2.33V (1.95%) check_circle OK
50 ft 12 AWG 2.94V (2.45%) check_circle OK
75 ft 10 AWG 2.77V (2.3%) check_circle OK
100 ft 8 AWG 2.31V (1.93%) check_circle OK
125 ft 8 AWG 2.89V (2.41%) check_circle OK
150 ft 8 AWG 3.47V (2.89%) check_circle OK
175 ft 6 AWG 2.56V (2.13%) check_circle OK
200 ft 6 AWG 2.92V (2.43%) check_circle OK
250 ft 4 AWG 2.29V (1.91%) check_circle OK
300 ft 4 AWG 2.75V (2.29%) check_circle OK
400 ft 3 AWG 2.91V (2.43%) check_circle OK
500 ft 2 AWG 2.88V (2.4%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.