Wire Size for 165.38 Amps

Typical copper and aluminum wire gauges for 165.38 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

165.38A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 2/0 AWG 4/0 AWG 0.7996V (0.6663%) check_circle OK
50 ft 2/0 AWG 4/0 AWG 1.6V (1.33%) check_circle OK
75 ft 2/0 AWG 4/0 AWG 2.4V (2%) check_circle OK
100 ft 2/0 AWG 4/0 AWG 3.2V (2.67%) check_circle OK
125 ft 3/0 AWG 4/0 AWG 3.17V (2.64%) check_circle OK
150 ft 4/0 AWG 300 kcmil 3.02V (2.51%) check_circle OK
175 ft 4/0 AWG 350 kcmil 3.52V (2.93%) check_circle OK
200 ft 250 kcmil 500 kcmil 3.41V (2.84%) check_circle OK
250 ft 300 kcmil 500 kcmil 3.55V (2.96%) check_circle OK
300 ft 500 kcmil 750 kcmil 2.56V (2.13%) check_circle OK
400 ft 500 kcmil no aluminum pick 3.41V (2.84%) check_circle OK
500 ft 750 kcmil no aluminum pick 2.83V (2.36%) check_circle OK

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.