Wire Size for 17.31 Amps

Typical copper wire gauges for 17.31 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 17.31A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

17.31A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 12 AWG 1.71V (1.43%) check_circle OK
50 ft 12 AWG 3.43V (2.86%) check_circle OK
75 ft 10 AWG 3.22V (2.68%) check_circle OK
100 ft 8 AWG 2.69V (2.24%) check_circle OK
125 ft 8 AWG 3.37V (2.81%) check_circle OK
150 ft 6 AWG 2.55V (2.12%) check_circle OK
175 ft 6 AWG 2.97V (2.48%) check_circle OK
200 ft 6 AWG 3.4V (2.83%) check_circle OK
250 ft 4 AWG 2.67V (2.22%) check_circle OK
300 ft 4 AWG 3.2V (2.67%) check_circle OK
400 ft 3 AWG 3.39V (2.83%) check_circle OK
500 ft 2 AWG 3.36V (2.8%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.