Wire Size for 17.5 Amps

Typical copper wire gauges for 17.5 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 17.5A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

17.5A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 12 AWG 1.73V (1.44%) check_circle OK
50 ft 12 AWG 3.47V (2.89%) check_circle OK
75 ft 10 AWG 3.26V (2.71%) check_circle OK
100 ft 8 AWG 2.72V (2.27%) check_circle OK
125 ft 8 AWG 3.4V (2.84%) check_circle OK
150 ft 6 AWG 2.58V (2.15%) check_circle OK
175 ft 6 AWG 3.01V (2.51%) check_circle OK
200 ft 6 AWG 3.44V (2.86%) check_circle OK
250 ft 4 AWG 2.7V (2.25%) check_circle OK
300 ft 4 AWG 3.23V (2.7%) check_circle OK
400 ft 3 AWG 3.43V (2.86%) check_circle OK
500 ft 2 AWG 3.4V (2.83%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.