Wire Size for 17.65 Amps

Typical copper wire gauges for 17.65 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 17.65A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

17.65A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 12 AWG 1.75V (1.46%) check_circle OK
50 ft 12 AWG 3.49V (2.91%) check_circle OK
75 ft 10 AWG 3.28V (2.74%) check_circle OK
100 ft 8 AWG 2.75V (2.29%) check_circle OK
125 ft 8 AWG 3.43V (2.86%) check_circle OK
150 ft 6 AWG 2.6V (2.17%) check_circle OK
175 ft 6 AWG 3.03V (2.53%) check_circle OK
200 ft 6 AWG 3.47V (2.89%) check_circle OK
250 ft 4 AWG 2.72V (2.27%) check_circle OK
300 ft 4 AWG 3.26V (2.72%) check_circle OK
400 ft 3 AWG 3.46V (2.88%) check_circle OK
500 ft 2 AWG 3.42V (2.85%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.