Wire Size for 17.72 Amps

Typical copper wire gauges for 17.72 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 17.72A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

17.72A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 12 AWG 1.75V (1.46%) check_circle OK
50 ft 12 AWG 3.51V (2.92%) check_circle OK
75 ft 10 AWG 3.3V (2.75%) check_circle OK
100 ft 8 AWG 2.76V (2.3%) check_circle OK
125 ft 8 AWG 3.45V (2.87%) check_circle OK
150 ft 6 AWG 2.61V (2.18%) check_circle OK
175 ft 6 AWG 3.05V (2.54%) check_circle OK
200 ft 6 AWG 3.48V (2.9%) check_circle OK
250 ft 4 AWG 2.73V (2.27%) check_circle OK
300 ft 4 AWG 3.27V (2.73%) check_circle OK
400 ft 3 AWG 3.47V (2.89%) check_circle OK
500 ft 2 AWG 3.44V (2.86%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.