Wire Size for 18.25 Amps

Typical copper wire gauges for 18.25 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 18.25A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

18.25A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 12 AWG 1.81V (1.51%) check_circle OK
50 ft 10 AWG 2.26V (1.89%) check_circle OK
75 ft 10 AWG 3.39V (2.83%) check_circle OK
100 ft 8 AWG 2.84V (2.37%) check_circle OK
125 ft 8 AWG 3.55V (2.96%) check_circle OK
150 ft 6 AWG 2.69V (2.24%) check_circle OK
175 ft 6 AWG 3.14V (2.61%) check_circle OK
200 ft 6 AWG 3.58V (2.99%) check_circle OK
250 ft 4 AWG 2.81V (2.34%) check_circle OK
300 ft 4 AWG 3.37V (2.81%) check_circle OK
400 ft 3 AWG 3.58V (2.98%) check_circle OK
500 ft 2 AWG 3.54V (2.95%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.