Wire Size for 18.48 Amps
Typical copper wire gauges for 18.48 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 18.48A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.
18.48A Wire Gauge by Distance
| Distance | Copper Gauge | V-Drop (Cu) | NEC Status |
|---|---|---|---|
| 25 ft | 12 AWG | 1.83V (1.52%) | OK |
| 50 ft | 10 AWG | 2.29V (1.91%) | OK |
| 75 ft | 10 AWG | 3.44V (2.86%) | OK |
| 100 ft | 8 AWG | 2.88V (2.4%) | OK |
| 125 ft | 8 AWG | 3.59V (3%) | OK |
| 150 ft | 6 AWG | 2.72V (2.27%) | OK |
| 175 ft | 6 AWG | 3.18V (2.65%) | OK |
| 200 ft | 4 AWG | 2.28V (1.9%) | OK |
| 250 ft | 4 AWG | 2.85V (2.37%) | OK |
| 300 ft | 4 AWG | 3.42V (2.85%) | OK |
| 400 ft | 2 AWG | 2.87V (2.39%) | OK |
| 500 ft | 2 AWG | 3.59V (2.99%) | OK |
Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.