Wire Size for 2.16 Amps

Typical copper wire gauges for 2.16 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 2.16A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

2.16A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.3391V (0.2826%) check_circle OK
50 ft 14 AWG 0.6782V (0.5652%) check_circle OK
75 ft 14 AWG 1.02V (0.8478%) check_circle OK
100 ft 14 AWG 1.36V (1.13%) check_circle OK
125 ft 14 AWG 1.7V (1.41%) check_circle OK
150 ft 14 AWG 2.03V (1.7%) check_circle OK
175 ft 14 AWG 2.37V (1.98%) check_circle OK
200 ft 14 AWG 2.71V (2.26%) check_circle OK
250 ft 14 AWG 3.39V (2.83%) check_circle OK
300 ft 12 AWG 2.57V (2.14%) check_circle OK
400 ft 12 AWG 3.42V (2.85%) check_circle OK
500 ft 10 AWG 2.68V (2.23%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.