Wire Size for 2.55 Amps

Typical copper wire gauges for 2.55 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 2.55A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

2.55A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.4004V (0.3336%) check_circle OK
50 ft 14 AWG 0.8007V (0.6673%) check_circle OK
75 ft 14 AWG 1.2V (1%) check_circle OK
100 ft 14 AWG 1.6V (1.33%) check_circle OK
125 ft 14 AWG 2V (1.67%) check_circle OK
150 ft 14 AWG 2.4V (2%) check_circle OK
175 ft 14 AWG 2.8V (2.34%) check_circle OK
200 ft 14 AWG 3.2V (2.67%) check_circle OK
250 ft 12 AWG 2.52V (2.1%) check_circle OK
300 ft 12 AWG 3.03V (2.52%) check_circle OK
400 ft 10 AWG 2.53V (2.11%) check_circle OK
500 ft 10 AWG 3.16V (2.64%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.