Wire Size for 2.61 Amps

Typical copper wire gauges for 2.61 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 2.61A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

2.61A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.4098V (0.3415%) check_circle OK
50 ft 14 AWG 0.8195V (0.683%) check_circle OK
75 ft 14 AWG 1.23V (1.02%) check_circle OK
100 ft 14 AWG 1.64V (1.37%) check_circle OK
125 ft 14 AWG 2.05V (1.71%) check_circle OK
150 ft 14 AWG 2.46V (2.05%) check_circle OK
175 ft 14 AWG 2.87V (2.39%) check_circle OK
200 ft 14 AWG 3.28V (2.73%) check_circle OK
250 ft 12 AWG 2.58V (2.15%) check_circle OK
300 ft 12 AWG 3.1V (2.58%) check_circle OK
400 ft 10 AWG 2.59V (2.16%) check_circle OK
500 ft 10 AWG 3.24V (2.7%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.