Wire Size for 2.8 Amps

Typical copper wire gauges for 2.8 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 2.8A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

2.8A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 14 AWG 0.4396V (0.3663%) check_circle OK
50 ft 14 AWG 0.8792V (0.7327%) check_circle OK
75 ft 14 AWG 1.32V (1.1%) check_circle OK
100 ft 14 AWG 1.76V (1.47%) check_circle OK
125 ft 14 AWG 2.2V (1.83%) check_circle OK
150 ft 14 AWG 2.64V (2.2%) check_circle OK
175 ft 14 AWG 3.08V (2.56%) check_circle OK
200 ft 14 AWG 3.52V (2.93%) check_circle OK
250 ft 12 AWG 2.77V (2.31%) check_circle OK
300 ft 12 AWG 3.33V (2.77%) check_circle OK
400 ft 10 AWG 2.78V (2.31%) check_circle OK
500 ft 10 AWG 3.47V (2.89%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.