Wire Size for 201.67 Amps

Typical copper and aluminum wire gauges for 201.67 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

201.67A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 4/0 AWG 250 kcmil 0.6131V (0.5109%) check_circle OK
50 ft 4/0 AWG 250 kcmil 1.23V (1.02%) check_circle OK
75 ft 4/0 AWG 250 kcmil 1.84V (1.53%) check_circle OK
100 ft 4/0 AWG 250 kcmil 2.45V (2.04%) check_circle OK
125 ft 4/0 AWG 300 kcmil 3.07V (2.55%) check_circle OK
150 ft 250 kcmil 500 kcmil 3.12V (2.6%) check_circle OK
175 ft 300 kcmil 500 kcmil 3.03V (2.52%) check_circle OK
200 ft 300 kcmil 500 kcmil 3.46V (2.88%) check_circle OK
250 ft 500 kcmil 750 kcmil 2.6V (2.17%) check_circle OK
300 ft 500 kcmil 750 kcmil 3.12V (2.6%) check_circle OK
400 ft 750 kcmil no aluminum pick 2.76V (2.3%) check_circle OK
500 ft 750 kcmil no aluminum pick 3.45V (2.87%) check_circle OK

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.