Wire Size for 21.23 Amps

Typical copper wire gauges for 21.23 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 21.23A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

21.23A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 10 AWG 1.32V (1.1%) check_circle OK
50 ft 10 AWG 2.63V (2.19%) check_circle OK
75 ft 8 AWG 2.48V (2.06%) check_circle OK
100 ft 8 AWG 3.3V (2.75%) check_circle OK
125 ft 6 AWG 2.61V (2.17%) check_circle OK
150 ft 6 AWG 3.13V (2.61%) check_circle OK
175 ft 4 AWG 2.29V (1.91%) check_circle OK
200 ft 4 AWG 2.62V (2.18%) check_circle OK
250 ft 4 AWG 3.27V (2.72%) check_circle OK
300 ft 3 AWG 3.12V (2.6%) check_circle OK
400 ft 2 AWG 3.29V (2.75%) check_circle OK
500 ft 1 AWG 3.27V (2.72%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.