Wire Size for 21.39 Amps

Typical copper wire gauges for 21.39 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 21.39A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

21.39A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 10 AWG 1.33V (1.11%) check_circle OK
50 ft 10 AWG 2.65V (2.21%) check_circle OK
75 ft 8 AWG 2.5V (2.08%) check_circle OK
100 ft 8 AWG 3.33V (2.77%) check_circle OK
125 ft 6 AWG 2.63V (2.19%) check_circle OK
150 ft 6 AWG 3.15V (2.63%) check_circle OK
175 ft 4 AWG 2.31V (1.92%) check_circle OK
200 ft 4 AWG 2.64V (2.2%) check_circle OK
250 ft 4 AWG 3.29V (2.75%) check_circle OK
300 ft 3 AWG 3.14V (2.62%) check_circle OK
400 ft 2 AWG 3.32V (2.77%) check_circle OK
500 ft 1 AWG 3.29V (2.75%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.