Wire Size for 21.82 Amps

Typical copper wire gauges for 21.82 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 21.82A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

21.82A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 10 AWG 1.35V (1.13%) check_circle OK
50 ft 10 AWG 2.71V (2.25%) check_circle OK
75 ft 8 AWG 2.55V (2.12%) check_circle OK
100 ft 8 AWG 3.4V (2.83%) check_circle OK
125 ft 6 AWG 2.68V (2.23%) check_circle OK
150 ft 6 AWG 3.21V (2.68%) check_circle OK
175 ft 4 AWG 2.35V (1.96%) check_circle OK
200 ft 4 AWG 2.69V (2.24%) check_circle OK
250 ft 4 AWG 3.36V (2.8%) check_circle OK
300 ft 3 AWG 3.21V (2.67%) check_circle OK
400 ft 2 AWG 3.39V (2.82%) check_circle OK
500 ft 1 AWG 3.36V (2.8%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.