Wire Size for 215 Amps

Typical copper and aluminum wire gauges for 215 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

215A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 4/0 AWG 300 kcmil 0.6536V (0.5447%) check_circle OK
50 ft 4/0 AWG 300 kcmil 1.31V (1.09%) check_circle OK
75 ft 4/0 AWG 300 kcmil 1.96V (1.63%) check_circle OK
100 ft 4/0 AWG 300 kcmil 2.61V (2.18%) check_circle OK
125 ft 4/0 AWG 350 kcmil 3.27V (2.72%) check_circle OK
150 ft 250 kcmil 500 kcmil 3.32V (2.77%) check_circle OK
175 ft 300 kcmil 500 kcmil 3.23V (2.69%) check_circle OK
200 ft 350 kcmil 750 kcmil 3.16V (2.63%) check_circle OK
250 ft 500 kcmil 750 kcmil 2.77V (2.31%) check_circle OK
300 ft 500 kcmil no aluminum pick 3.33V (2.77%) check_circle OK
400 ft 750 kcmil no aluminum pick 2.94V (2.45%) check_circle OK
500 ftExceeds available gauges

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.