Wire Size for 23.48 Amps

Typical copper wire gauges for 23.48 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 23.48A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

23.48A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 10 AWG 1.46V (1.21%) check_circle OK
50 ft 10 AWG 2.91V (2.43%) check_circle OK
75 ft 8 AWG 2.74V (2.28%) check_circle OK
100 ft 6 AWG 2.31V (1.92%) check_circle OK
125 ft 6 AWG 2.88V (2.4%) check_circle OK
150 ft 6 AWG 3.46V (2.88%) check_circle OK
175 ft 4 AWG 2.53V (2.11%) check_circle OK
200 ft 4 AWG 2.89V (2.41%) check_circle OK
250 ft 3 AWG 2.88V (2.4%) check_circle OK
300 ft 3 AWG 3.45V (2.88%) check_circle OK
400 ft 1 AWG 2.89V (2.41%) check_circle OK
500 ft 1/0 AWG 2.86V (2.39%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.