Wire Size for 26.47 Amps
Typical copper wire gauges for 26.47 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 26.47A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.
26.47A Wire Gauge by Distance
| Distance | Copper Gauge | V-Drop (Cu) | NEC Status |
|---|---|---|---|
| 25 ft | 10 AWG | 1.64V (1.37%) | OK |
| 50 ft | 10 AWG | 3.28V (2.74%) | OK |
| 75 ft | 8 AWG | 3.09V (2.57%) | OK |
| 100 ft | 6 AWG | 2.6V (2.17%) | OK |
| 125 ft | 6 AWG | 3.25V (2.71%) | OK |
| 150 ft | 4 AWG | 2.45V (2.04%) | OK |
| 175 ft | 4 AWG | 2.85V (2.38%) | OK |
| 200 ft | 4 AWG | 3.26V (2.72%) | OK |
| 250 ft | 3 AWG | 3.24V (2.7%) | OK |
| 300 ft | 2 AWG | 3.08V (2.57%) | OK |
| 400 ft | 1 AWG | 3.26V (2.72%) | OK |
| 500 ft | 1/0 AWG | 3.23V (2.69%) | OK |
Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.
Also Calculate
Other Amperages
This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.