Wire Size for 26.4 Amps

Typical copper wire gauges for 26.4 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 26.4A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

26.4A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 10 AWG 1.64V (1.36%) check_circle OK
50 ft 10 AWG 3.27V (2.73%) check_circle OK
75 ft 8 AWG 3.08V (2.57%) check_circle OK
100 ft 6 AWG 2.59V (2.16%) check_circle OK
125 ft 6 AWG 3.24V (2.7%) check_circle OK
150 ft 4 AWG 2.44V (2.03%) check_circle OK
175 ft 4 AWG 2.85V (2.37%) check_circle OK
200 ft 4 AWG 3.25V (2.71%) check_circle OK
250 ft 3 AWG 3.23V (2.7%) check_circle OK
300 ft 2 AWG 3.07V (2.56%) check_circle OK
400 ft 1 AWG 3.25V (2.71%) check_circle OK
500 ft 1/0 AWG 3.22V (2.68%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.