Wire Size for 265 Amps

Typical copper and aluminum wire gauges for 265 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

265A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 300 kcmil 500 kcmil 0.5684V (0.4737%) check_circle OK
50 ft 300 kcmil 500 kcmil 1.14V (0.9474%) check_circle OK
75 ft 300 kcmil 500 kcmil 1.71V (1.42%) check_circle OK
100 ft 300 kcmil 500 kcmil 2.27V (1.89%) check_circle OK
125 ft 300 kcmil 500 kcmil 2.84V (2.37%) check_circle OK
150 ft 300 kcmil 500 kcmil 3.41V (2.84%) check_circle OK
175 ft 350 kcmil 750 kcmil 3.4V (2.84%) check_circle OK
200 ft 500 kcmil 750 kcmil 2.73V (2.28%) check_circle OK
250 ft 500 kcmil no aluminum pick 3.42V (2.85%) check_circle OK
300 ft 750 kcmil no aluminum pick 2.72V (2.27%) check_circle OK
400 ftExceeds available gauges
500 ftExceeds available gauges

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.