Wire Size for 27.17 Amps

Typical copper wire gauges for 27.17 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. At 27.17A the load sits in residential-branch territory where aluminum is not a typical conductor, so the table lists copper only. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

27.17A Wire Gauge by Distance

DistanceCopper GaugeV-Drop (Cu)NEC Status
25 ft 10 AWG 1.68V (1.4%) check_circle OK
50 ft 10 AWG 3.37V (2.81%) check_circle OK
75 ft 8 AWG 3.17V (2.64%) check_circle OK
100 ft 6 AWG 2.67V (2.22%) check_circle OK
125 ft 6 AWG 3.34V (2.78%) check_circle OK
150 ft 4 AWG 2.51V (2.09%) check_circle OK
175 ft 4 AWG 2.93V (2.44%) check_circle OK
200 ft 4 AWG 3.35V (2.79%) check_circle OK
250 ft 3 AWG 3.33V (2.77%) check_circle OK
300 ft 2 AWG 3.16V (2.64%) check_circle OK
400 ft 1 AWG 3.35V (2.79%) check_circle OK
500 ft 1/0 AWG 3.31V (2.76%) check_circle OK

Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.

Other Amperages

This calculator provides estimates for reference purposes only. Always consult a licensed electrician and verify compliance with the National Electrical Code (NEC) and local electrical codes before performing any electrical work.