Wire Size for 280 Amps

Typical copper and aluminum wire gauges for 280 amps across common run lengths on a 120V circuit, sized to keep voltage drop under 3% and respect the NEC 240.4(D) small-conductor rule. Actual install sizing depends on conductor material, insulation/termination temperature rating, cable type, ambient and bundling derates, and local code.

280A Wire Gauge by Distance

DistanceCopper GaugeAluminum GaugeV-Drop (Cu)NEC Status
25 ft 300 kcmil 500 kcmil 0.6006V (0.5005%) check_circle OK
50 ft 300 kcmil 500 kcmil 1.2V (1%) check_circle OK
75 ft 300 kcmil 500 kcmil 1.8V (1.5%) check_circle OK
100 ft 300 kcmil 500 kcmil 2.4V (2%) check_circle OK
125 ft 300 kcmil 500 kcmil 3V (2.5%) check_circle OK
150 ft 350 kcmil 500 kcmil 3.08V (2.57%) check_circle OK
175 ft 350 kcmil 750 kcmil 3.6V (3%) check_circle OK
200 ft 500 kcmil 750 kcmil 2.89V (2.41%) check_circle OK
250 ft 750 kcmil no aluminum pick 2.39V (2%) check_circle OK
300 ft 750 kcmil no aluminum pick 2.87V (2.39%) check_circle OK
400 ftExceeds available gauges
500 ftExceeds available gauges

Aluminum is not typical for 10 AWG and smaller branch-circuit conductors in residential settings. Copper gauges use the NEC 240.4(D) branch-circuit cap, not raw 75°C ampacity.